    Brand Name : SIEMENS
    Model Number : 6ES7518-4AP00-3AB0
    Certification : CE
    Price : USD
    Payment Terms : L/C, T/T
    Supply Ability : 100
    Delivery Time : 10-12Days
    • Product Details
    • Company Profile

    SIEMENS 6ES7518-4AP00-3AB0 PROFINET RT, 3RD INTERFACE: PROFINET BASIC SERVICES, 4TH INTERFACE: PROFIBUS

    SIEMENS 6ES7518-4AP00-3AB0 PROFINET RT, 3RD INTERFACE: PROFINET BASIC SERVICES, 4TH INTERFACE: PROFIBUS

    SIEMENS 6ES7518-4AP00-3AB0 MODULE INFORMATION
    SIEMENS 6ES7518-4AP00-3AB0 IS A MODULAR CONTROLLER FROM THE SIMATIC S7-1500 SERIES. It has the following characteristics:

    The first interface: P ROFINET RT (Real Time) for real-time communication.
    The second interface: PROFINET IRT (Isolated Real Time) with cross-border swapping for isolation and increased reliability of real-time communication.
    The third interface: PROFINET basic services, which are used to provide additional network functions.
    The fourth interface, PROFIBUS, is used to communicate with existing PROFIBUS network devices.
    Performance: 1 ns bit performance, meaning it is capable of handling data rates up to 1 Gbit/s.
    Memory card requirements: Use SIMATIC Memory Card, a storage medium for storing programs and data.
    The module is suitable for applications that require simultaneous support for several industrial communication protocols, such as the integration of PROFINET and PROFIBUS devices in a single system, or where high-performance real-time communication is required

    General information
    Product type designationCPU 1518-4 PN/DP ODK
    HW functional statusFS10
    Firmware versionV2.9
    Product function
    ● I&M dataYes; I&M0 to I&M3
    ● Isochronous modeYes; Distributed and central; with minimum OB 6x cycle of 125 µs (distributed) and 1 ms (central)
    Engineering with
    ● STEP 7 TIA Portal configurable/integrated from versionV17 (FW V2.9) / V14 (FW V2.0) or higher
    Configuration control
    via datasetYes
    Display
    Screen diagonal [cm]6.1 cm
    Control elements
    Number of keys6
    Mode selector switch1
    Supply voltage
    Rated value (DC)24 V
    permissible range, lower limit (DC)19.2 V
    permissible range, upper limit (DC)28.8 V
    Reverse polarity protectionYes
    Mains buffering
    ● Mains/voltage failure stored energy time5 ms
    Input current
    Current consumption (rated value)1.55 A
    Inrush current, max.2.4 A; Rated value
    I²t0.02 A²·s
    Power
    Infeed power to the backplane bus12 W
    Power consumption from the backplane bus (balanced)30 W
    Power loss
    Power loss, typ.24 W
    Memory
    Number of slots for SIMATIC memory card1
    SIMATIC memory card requiredYes
    Work memory
    ● integrated (for program)6 Mbyte
    ● integrated (for data)60 Mbyte
    ● integrated (for CPU function library of CPU Runtime)50 Mbyte; Note: The "CPU function library of the CPU" are C/C++ blocks for the user program that were created using the SIMATIC ODK 1500S or Target 1500S.
    Load memory
    ● Plug-in (SIMATIC Memory Card), max.32 Gbyte
    Backup
    ● maintenance-freeYes
    CPU processing times
    for bit operations, typ.1 ns
    for word operations, typ.2 ns
    for fixed point arithmetic, typ.2 ns
    for floating point arithmetic, typ.6 ns
    CPU-blocks
    Number of elements (total)20 000; Blocks (OB, FB, FC, DB) and UDTs
    DB
    ● Number range1 ... 60 999; subdivided into: number range that can be used by the user: 1 ... 59 999, and number range of DBs created via SFC 86: 60 000 ... 60 999
    ● Size, max.16 Mbyte; For DBs with absolute addressing, the max. size is 64 KB
    FB
    ● Number range0 ... 65 535
    ● Size, max.1 Mbyte
    FC
    ● Number range0 ... 65 535
    ● Size, max.1 Mbyte
    OB
    ● Size, max.1 Mbyte
    ● Number of free cycle OBs100
    ● Number of time alarm OBs20
    ● Number of delay alarm OBs20
    ● Number of cyclic interrupt OBs20; with minimum OB 3x cycle of 100 µs
    ● Number of process alarm OBs50
    ● Number of DPV1 alarm OBs3
    ● Number of isochronous mode OBs3
    ● Number of technology synchronous alarm OBs2
    ● Number of startup OBs100
    ● Number of asynchronous error OBs4
    ● Number of synchronous error OBs2
    ● Number of diagnostic alarm OBs1
    Nesting depth
    ● per priority class24
    Counters, timers and their retentivity
    S7 counter
    ● Number2 048
    Retentivity
    — adjustableYes
    IEC counter
    ● NumberAny (only limited by the main memory)
    Retentivity
    — adjustableYes
    S7 times
    ● Number2 048
    Retentivity
    — adjustableYes
    IEC timer
    ● NumberAny (only limited by the main memory)
    Retentivity
    — adjustableYes
    Data areas and their retentivity
    Retentive data area (incl. timers, counters, flags), max.768 kbyte; In total; available retentive memory for bit memories, timers, counters, DBs, and technology data (axes): 700 KB
    Extended retentive data area (incl. timers, counters, flags), max.20 Mbyte; When using PS 6 0W 24/48/60 V DC HF
    Flag
    ● Size, max.16 kbyte
    ● Number of clock memories8; 8 clock memory bit, grouped into one clock memory byte
    Data blocks
    ● Retentivity adjustableYes
    ● Retentivity presetNo
    Local data
    ● per priority class, max.64 kbyte; max. 16 KB per block
    Address area
    Number of IO modules16 384; max. number of modules / submodules
    I/O address area
    ● Inputs32 kbyte; All inputs are in the process image
    ● Outputs32 kbyte; All outputs are in the process image
    per integrated IO subsystem
    — Inputs (volume)32 kbyte; max. 32 KB via X1; max. 8 KB via X2 or X4
    — Outputs (volume)32 kbyte; max. 32 KB via X1; max. 8 KB via X2 or X4
    per CM/CP
    — Inputs (volume)8 kbyte
    — Outputs (volume)8 kbyte
    Subprocess images
    ● Number of subprocess images, max.32
    Hardware configuration
    Number of distributed IO systems64; A distributed I/O system is characterized not only by the integration of distributed I/O via PROFINET or PROFIBUS communication modules, but also by the connection of I/O via AS-i master modules or links (e.g. IE/PB-Link)
    Number of DP masters
    ● integrated1
    ● Via CM8; A maximum of 8 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total
    Number of IO Controllers
    ● integrated2
    ● Via CM8; A maximum of 8 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total
    Rack
    ● Modules per rack, max.32; CPU + 31 modules
    PtP CM
    ● Number of PtP CMsthe number of connectable PtP CMs is only limited by the number of available slots
    Time of day
    Clock
    ● TypeHardware clock
    ● Backup time6 wk; At 40 °C ambient temperature, typically
    ● Deviation per day, max.10 s; Typ.: 2 s
    Operating hours counter
    ● Number16
    Clock synchronization
    ● supportedYes
    ● to DP, masterYes
    ● in AS, masterYes
    ● in AS, slaveYes
    ● on Ethernet via NTPYes
    Interfaces
    Number of PROFINET interfaces3
    Number of PROFIBUS interfaces1
    1. Interface
    Interface types
    ● RJ 45 (Ethernet)Yes; X1
    ● Number of ports2
    ● integrated switchYes
    Protocols
    ● IP protocolYes; IPv4
    ● PROFINET IO ControllerYes
    ● PROFINET IO DeviceYes
    ● SIMATIC communicationYes
    ● Open IE communicationYes; Optionally also encrypted
    ● Web serverYes
    ● Media redundancyYes
    PROFINET IO Controller
    Services
    — PG/OP communicationYes
    — Isochronous modeYes
    — Direct data exchangeYes; Requirement: IRT and isochronous mode (MRPD optional)
    — IRTYes
    — PROFIenergyYes; per user program
    — Prioritized startupYes; Max. 32 PROFINET devices
    — Number of connectable IO Devices, max.512; In total, up to 1 000 distributed I/O devices can be connected via AS-i, PROFIBUS or PROFINET
    — Of which IO devices with IRT, max.64
    — Number of connectable IO Devices for RT, max.512
    — of which in line, max.512
    — Number of IO Devices that can be simultaneously activated/deactivated, max.8; in total across all interfaces

    SIEMENS 6ES7518-4AP00-3AB0 PROFINET RT, 3RD INTERFACE: PROFINET BASIC SERVICES, 4TH INTERFACE: PROFIBUS

    Quality SIEMENS 6ES7518-4AP00-3AB0 PROFINET RT, 3RD INTERFACE: PROFINET BASIC SERVICES, 4TH INTERFACE: PROFIBUS for sale
    Inquiry Cart 0
    Send your message to this supplier
     
    *From:
    *To: Shenzhen Voboal Industrial Automation Co., Ltd.
    *Subject:
    *Message:
    Characters Remaining: (0/3000)