Sign In | Join Free | My burrillandco.com |
|
Ask Lasest Price | |
Brand Name : | IFM |
Model Number : | LR2050 |
Certification : | CE |
Payment Terms : | L/C, T/T |
Supply Ability : | 100 |
Delivery Time : | 10-12Days |
IFM Continuous level sensor (guided wave radar) LR2050
LR0000B-ER34AKSKG/US
Okay, let's take a look at the details of the IFM Continuous Level
Sensor (Guided Wave Radar) LR2050 LR0000B-ER34AKSKG/US:
1. Product Name:
- IFM Continuous Level Sensor (Guided Wave Radar) LR2050
LR0000B-ER34AKSKG/US
2. Description:
- The LR2050 LR0000B-ER34AKSKG/US is a continuous level sensor from
IFM Electronics that uses guided wave radar technology.
- Guided wave radar level sensors are used to provide continuous
measurement of the level of liquids, slurries, and solids in
industrial applications.
3. Key Features:
- Guided wave radar technology for accurate and reliable level
measurement
- Stainless steel housing and process connection for use in harsh
environments
- 4-20 mA analog output and HART communication protocol
- Compact and easy to install design
- Protection rating of IP68/IP69K for submerged and high-pressure
applications
4. Applications:
- The IFM LR2050 LR0000B-ER34AKSKG/US guided wave radar level
sensor is suitable for a wide range of industrial applications,
such as:
- Level measurement in storage tanks, silos, and process vessels
- Continuous monitoring of liquid and solid levels
- Process control and optimization in the food, chemical, and oil
and gas industries
5. Connectivity:
- The sensor has a 4-wire DC connection:
- 1 x Brown (L+)
- 1 x Blue (L-)
- 1 x Black (4-20 mA analog output)
- 1 x White (HART communication)
- The sensor can be easily integrated into industrial control
systems and automation networks.
6. Capabilities:
- Guided wave radar technology for accurate and reliable level
measurement
- Stainless steel housing and process connection for use in harsh
environments
- 4-20 mA analog output and HART communication protocol for
integration with control systems
- Compact and easy to install design with IP68/IP69K protection
rating
7. Compatibility:
- The IFM LR2050 LR0000B-ER34AKSKG/US guided wave radar level
sensor is designed to be compatible with a wide range of industrial
automation and control systems.
- It can be integrated with programmable logic controllers (PLCs),
SCADA systems, and other industrial control equipment.
The LR2050 LR0000B-ER34AKSKG/US is a versatile and reliable
continuous level sensor from IFM Electronics, using guided wave
radar technology to provide accurate and reliable level measurement
in a variety of industrial applications. Its stainless steel
housing, 4-20 mA analog output, and HART communication capabilities
make it suitable for use in harsh environments and easy integration
with industrial control systems.
If you have any further questions about the IFM LR2050
LR0000B-ER34AKSKG/US guided wave radar level sensor or need
additional information, please don't hesitate to ask.
Product characteristics
Number of inputs and outputs | Number of digital outputs: 1; Number of analogue outputs: 1 |
Probe length L [mm] | 150...2000 |
Process connection | threaded connection G 3/4 external thread |
Application
Special feature | Gold-plated contacts |
Application | for industrial applications |
Media | Liquids |
Dielectric constant of the medium | ≥ 1,8; (for media with a dielectric constant of 1.8...5 (e.g. oils), a coaxial pipe is needed for operation) |
Recommended media | water; hydrous media; oils; oil-based media |
Process temperature [°C] | -20...100; (see note under remarks) |
Pressure rating [bar] | 16 |
Vacuum resistance [mbar] | -1000 |
MAWP (for applications according to CRN) [bar] | 16 |
Electrical data
Operating voltage [V] | 18...30 DC |
Current consumption [mA] | < 50 |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | < 3 |
Measuring principle | guided wave radar |
Inputs / outputs
Number of inputs and outputs | Number of digital outputs: 1; Number of analogue outputs: 1 |
Outputs
Total number of outputs | 2 |
Output signal | switching signal; analogue signal; IO-Link |
Electrical design | PNP/NPN |
Number of digital outputs | 1 |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] | 2.5 |
Permanent current rating of switching output DC [mA] | 150; (200 (...60 °C)) |
Number of analogue outputs | 1 |
Analogue current output [mA] | 4...20, invertible; (scalable) |
Max. load [Ω] | 500 |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Measuring/setting range
Probe length L [mm] | 150...2000 |
Active range A [mm] | L-40 (L-60); (when set to oil and oil based media) |
Inactive range I1 / I2 [mm] | 30 / 10 (30); (when set to oil and oil based media) |
Sampling rate [Hz] | 4 |
Setting range
Set point SP [mm] | 15...L-30 | |
Note on setpoint SP |
| |
Reset point rP [mm] | 10... L-35 | |
Note on reset point rP |
| |
In steps of [mm] | 1 | |
Hysteresis [mm] | > 5 |
Accuracy / deviations
Measuring error [mm] | ± 7 |
Offset error [mm] | 5 |
Resolution [mm] | 1 |
Zero signal (current) [mA] | 4.0 |
Full signal (current) [mA] | 20 |
Temperature drift per 10 K | ± 0.2 % |
![]() |